        關于低壓抽屜柜安裝規范,我國是統一規定的。根據變電所低壓配電室的配電設備布置,應符合我國標準《10kV及以下變電所設計規范》(GB50053-94)的規定。關于低壓抽屜柜能否靠墻安裝,里面有明確的規定。敲黑板,劃,不能!不能!不能!重要的事情說三遍。
        The installation specification of low-voltage drawer cabinet is unified by the state. According to the distribution equipment layout of the low-voltage distribution room of the substation, it should comply with the national standard "code for design of 10kV and below substations" (GB 50053-94). There are clear regulations about whether the low-voltage drawer cabinet can be installed against the wall. Knock on the blackboard, draw the point, no! No! No! Important things are to be repeated for 3 times.
        雖然,有些低壓抽屜柜廠家說明中是可以靠墻安裝的,而且一部分低壓柜型號的產品,所有接線都是柜前操作,柜后面是封閉的,靠不靠墻似乎沒啥影響。但是考慮到巡視、檢修、通風散熱考慮,開關柜與墻需要保持一定的距離。而且規定就是規定,在規定沒有更改之前,任何人不要有僥幸心理。萬一出了事故,違規安裝的責任誰也承擔不起。
        Although, some low-voltage drawer cabinet manufacturers can be installed against the wall, and part of the low-voltage cabinet model products, all wiring is in front of the cabinet operation, the back of the cabinet is closed, it seems that there is no influence whether it is against the wall or not. However, considering the inspection, maintenance, ventilation and heat dissipation, the switch cabinet and the wall need to keep a certain distance. And the rule is the rule. Before the rule is changed, no one should take chances. In case of an accident, no one can bear the responsibility of illegal installation.
        關于MNS低壓抽屜柜的安裝規范還有以下規定:
        The installation specification of MNS low-voltage drawer cabinet also has the following provisions:
        1·配電室的位置應靠近用電負荷中心,設置在塵埃少、腐蝕介質少、干燥和震動輕微的地方,并宜適當留有發展余地。
        1. The distribution room should be located close to the power load center, where there is less dust, less corrosive medium, dry and slight vibration, and there should be room for development.
                                    MNS低壓抽屜柜
        2·配電設備的布置必須遵循、可靠、適用和經濟等原則,并應便于安裝、操作、搬運、檢修、試驗和監測。
        2. The layout of distribution equipment must follow the principles of safety, reliability, applicability and economy, and should be convenient for installation, operation, handling, maintenance, test and monitoring.
        3·配電室內除本室需用的管道外,不應有其它的管道通過。室內管道上不應設置閥門和中間接頭;水汽管道與散熱器的連接應采用焊接。配電屏的上方不應敷設管道。
        3. In the power distribution room, there should be no other pipes except the pipes needed in the room. Valve and intermediate joint shall not be set on indoor pipeline; the connection between water vapor pipeline and radiator shall be welded. No pipe shall be laid above the distribution panel.
        4·落地式配電箱的底部宜抬高,室內宜高出地面 50mm 以上,室外應高出地面200mm 以上。底座周圍應采取封閉措施,并應能防止鼠、蛇類等小動物進入箱內。
        4. The bottom of floor type distribution box should be raised, indoor should be higher than the ground by more than 50 mm, outdoor should be higher than the ground by more than 200 mm. Sealing measures shall be taken around the base to prevent mice, snakes and other small animals from entering the box.
        5·同一配電室內并列的兩段母線,當任一段母線有一級負荷時,母線分段處應設防火隔斷措施。
        5. For two sections of bus in parallel in the same distribution room, when any section of bus has first-class load, fire isolation measures shall be set at the section of bus.
        6·當高壓及低壓配電設備設在同一室內時,且二者有一側柜頂有裸露的母線,二者之間的凈距不應小于 2m。
        6. When the high-voltage and low-voltage distribution equipment are located in the same room, and there is an exposed bus on one side of the cabinet top, the clear distance between the two should not be less than 2m.
        7·成排布置的配電屏,其長度超過 6m 時,屏后的通道應設兩個出口,并宜布置在通道的兩端,當兩出口之間的距離超過15m 時,其間尚應增加出口。
        7. When the length of the distribution panel arranged in rows exceeds 6m, the channel behind the panel should be set with two outlets, which should be arranged at both ends of the channel. When the distance between the two outlets exceeds 15m, there should be more outlets between them.
        8·成排布置的配電屏,其屏前和屏后的通道小寬度應符合下表的規定。
        8. The minimum width of the channel in front of and behind the distribution panel arranged in rows shall meet the requirements of the following table.
        首頁首頁 產品產品 電話電話 置頂置頂
        主站蜘蛛池模板: 日本一区二区三深夜不卡| 亚洲av乱码一区二区三区| 日韩av一区二区三区在线播放| 庆云县| 中文字幕亚洲精品第1页| 久久丫精品忘忧草西安产品| 日日摸日日碰人妻无码老牲| 国产伦视频一区二区三区| 亚洲蜜桃av一区二区三区| 成年女人A级毛片免| 午夜精品射精入后重之免费观看 | 老熟妇仑乱视频一区二区| 亚洲AV成人午夜福利在线观看| 一二三四中文字幕日韩乱码| 蛟河市| 国产精品98福利小视频| 亚洲美免无码中文字幕在线| 亚洲精品456在线| 日本一区二区在线视观看| 综合无码一区二区三区四区五区| 99热这里只有精品国产66| 免费 黄 色 人成 视频 在 线| 少妇高潮大叫好爽喷水| 激情综合五月天开心久久| 大白屁股流白浆一区二区三区 | 亚洲一区二区国产精品视频| 亚洲一区二区三区香蕉| 人人超碰人人爱超碰国产| 国产一级r片内射免费视频| 97人妻精品一区二区三区免| 欧美日韩一区二区成人午夜电影| 国产成本人片无码免费2020| 草莓视频中文字幕人妻系列| 久久这里只有精品少妇| 亚洲欧洲日产国码二区在线| 无遮挡高潮国产免费观看| 91免费国产高清在线| 亚洲精品中文字幕尤物综合| 国产精品美女久久久久久麻豆| 久久精品国产精品亚洲综合| 亚洲国产av一区二区三|